0.6/1kV CVV-SWA IEC 60502(2-16core)

0.6/1kV CVV-SWA IEC 60502(2-16core)

basic information
Detail
Application:
For supervisory electrical equipment, station, control circuits, outdoor, suitable installation in dry or wet cable troches
Conductor:
Concentric Stranded copper wire
Insulation:PVC Black color
Identification:Printed White number on the surface of Black insulation
Filler:Suitable filler
Binding tape:Suitable tape
Inner sheath:PVC Black color
Shield:Annealed copper tape
Binding tape:Suitable tape
Outer Sheath:PVC Black color

 

2 Core CVV-S Control Cable


No.of core

Nominal cross- sectional area sq.mm²

No.&dia. of wires No./mm

Thickness of insulation mm

Thickness of inner sheath mm

Thickness of outer sheath mm

Overall diameter (Approx.)
mm

Maximum conductor resistance (at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

2

0.5

7×0.30

0.8

1

1.8

12.5

36

0.0162

180

0.75

7×0.37

0.8

1

1.8

13

24.5

0.0142

195

1

7×0.40

0.8

1

1.8

13

18.1

0.0135

205

1.5

7×0.50

0.8

1

1.8

14

12.1

0.0115

230

2.5

7×0.67

0.8

1

1.8

15

7.41

0.0093

280

4

7×0.85

1

1

1.8

17

4.61

0.0092

375

6

7×1.04

1

1

1.8

18.5

3.08

0.0078

450

3 Core CVV-S Control Cable


No.of core

Nominal cross- sectional area sq.mm²

No.&dia. of wires No./mm

Thickness of insulation mm

Thickness of inner sheath mm

Thickness of outer sheath mm

Overall diameter(Approx.)
mm

Maximum conductor resistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

3

0.5

7×0.30

0.8

1

1.8

13

36

0.0162

195

0.75

7×0.37

0.8

1

1.8

13.5

24.5

0.0142

215

1

7×0.40

0.8

1

1.8

13.5

18.1

0.0135

225

1.5

7×0.50

0.8

1

1.8

14.5

12.1

0.0115

260

2.5

7×0.67

0.8

1

1.8

15.5

7.41

0.0093

325

4

7×0.85

1

1

1.8

18

4.61

0.0092

445

6

7×1.04

1

1

1.8

19

3.08

0.0078

545



4 Core CVV-S Control Cable


No.of core

Nominal cross- sectional area sq.mm²

No.&dia. of wires No./mm

Thickness of insulation mm

Thickness of inner sheath mm

Thickness of outer sheath mm

Overall diameter(Approx.)
mm

Maximum conductor resistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

4

0.5

7×0.30

0.8

1

1.8

13.5

36

0.0162

220

0.75

7×0.37

0.8

1

1.8

14

24.5

0.0142

245

1

7×0.40

0.8

1

1.8

14.5

18.1

0.0135

260

1.5

7×0.50

0.8

1

1.8

15.5

12.1

0.0115

300

2.5

7×0.67

0.8

1

1.8

16.5

7.41

0.0093

385

4

7×0.85

1

1

1.8

19

4.61

0.0092

530

6

7×1.04

1

1

1.8

20.5

3.08

0.0078

660

5 Core CVV-S Control Cable


No.of core

Nominalcross- sectionalarea sq.mm²

No.&dia. of wires No./mm

Thicknessof insulationmm

Thicknessof inner sheath mm

Thicknessof outer sheath mm

Overall diameter(Approx.)
mm

Maximumconductorresistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cableweight
(Approx.)
kg/km

5

0.5

7×0.30

0.8

1

1.8

14.5

36

0.0162

250

0.75

7×0.37

0.8

1

1.8

15

24.5

0.0142

280

1

7×0.40

0.8

1

1.8

15.5

18.1

0.0135

295

1.5

7×0.50

0.8

1

1.8

16.5

12.1

0.0115

345

2.5

7×0.67

0.8

1

1.8

18

7.41

0.0093

445

4

7×0.85

1

1

1.8

20.5

4.61

0.0092

620

6

7×1.04

1

1

1.8

22.5

3.08

0.0078

780

6 Core CVV-S Control Cable


No.of core

Nominalcross- sectionalarea sq.mm²

No.&dia. Of wires No./mm

Thicknessof insulationmm

Thicknessof inner sheath mm

Thicknessof outer sheath mm

Overall diameter(Approx.)
mm

Maximumconductorresistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

6

0.5

7×0.30

0.8

1

1.8

15.5

36

0.0162

270

0.75

7×0.37

0.8

1

1.8

16

24.5

0.0142

305

1

7×0.40

0.8

1

1.8

16.5

18.1

0.0135

320

1.5

7×0.50

0.8

1

1.8

17.5

12.1

0.0115

375

2.5

7×0.67

0.8

1

1.8

19

7.41

0.0093

290

4

7×0.85

1

1

1.8

22

4.61

0.0092

685

6

7×1.04

1

1

1.8

24

3.08

0.0078

865



7 Core CVV-S Control Cable


No.of core

Nominalcross- sectionalarea sq.mm²

No.&dia. Of wires No./mm

Thicknessof insulationmm

Thicknessof inner sheath mm

Thicknessof outer sheath mm

Overall diameter(Approx.)
mm

Maximumconductorresistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

7

0.5

7×0.30

0.8

1

1.8

15.5

36

0.0162

275

0.75

7×0.37

0.8

1

1.8

16

24.5

0.0142

315

1

7×0.40

0.8

1

1.8

16.5

18.1

0.0135

330

1.5

7×0.50

0.8

1

1.8

17.5

12.1

0.0115

395

2.5

7×0.67

0.8

1

1.8

19

7.41

0.0093

520

4

7×0.85

1

1

1.8

22

4.61

0.0092

730

6

7×1.04

1

1

1.8

24

3.08

0.0078

930

8 Core CVV-S Control Cable


No.of core

Nominalcross- sectionalarea sq.mm²

No.&dia. of wires No./mm

Thicknessof insulationmm

Thicknessof inner sheathmm

Thicknessof outer sheath mm

Overall diameter(Approx.)
mm

Maximumconductorresistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

8

0.5

7×0.30

0.8

1

1.8

16

36

0.0162

310

0.75

7×0.37

0.8

1

1.8

17

24.5

0.0142

350

1

7×0.40

0.8

1

1.8

17

18.1

0.0135

370

1.5

7×0.50

0.8

1

1.8

18.5

12.1

0.0115

445

2.5

7×0.67

0.8

1

1.8

20

7.41

0.0093

590

4

7×0.85

1

1

1.8

23.5

4.61

0.0092

835

6

7×1.04

1

1

1.8

25.5

3.08

0.0078

1070

9 Core CVV-S Control Cable


No.of core

Nominalcross- sectionalarea sq.mm²

No.&dia. Of wires No./mm

Thicknessof insulationmm

Thicknessof inner sheath mm

Thicknessof outer sheath mm

Overall diameter(Approx.)
mm

Maximumconductorresistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

9

0.5

7×0.30

0.8

1

1.8

17

36

0.0162

340

0.75

7×0.37

0.8

1

1.8

18

24.5

0.0142

390

1

7×0.40

0.8

1

1.8

18

18.1

0.0135

415

1.5

7×0.50

0.8

1

1.8

19.5

12.1

0.0115

495

2.5

7×0.67

0.8

1

1.8

21.5

7.41

0.0093

660

4

7×0.85

1

1

1.8

25

4.61

0.0092

945

6

7×1.04

1

1

1.8

27.5

3.08

0.0078

1215



10 Core CVV-S Control Cable


No.of core

Nominalcross- sectionalarea sq.mm²

No.&dia. Of wires No./mm

Thicknessof insulationmm

Thicknessof inner sheath mm

Thicknessof outer sheath mm

Overall diameter(Approx.)
mm

Maximumconductorresistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

10

0.5

7×0.30

0.8

1

1.8

18

36

0.0162

370

0.75

7×0.37

0.8

1

1.8

19

24.5

0.0142

425

1

7×0.40

0.8

1

1.8

19.5

18.1

0.0135

445

1.5

7×0.50

0.8

1

1.8

20.5

12.1

0.0115

540

2.5

7×0.67

0.8

1

1.8

23

7.41

0.0093

720

4

7×0.85

1

1

1.8

27

4.61

0.0092

1030

6

7×1.04

1

1

1.8

29.5

3.08

0.0078

1325

11 Core CVV-S Control Cable


No.of core

Nominal cross -sectioal area sq.mm²

No.&dia. Of wires No./mm

Thicknessof insulationmm

Thicknessof inner sheath mm

Thicknessof outer sheath mm

Overall diameter(Approx.)
mm

Maximumconductorresistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

11

0.5

7×0.30

0.8

1

1.8

18.5

36

0.0162

395

0.75

7×0.37

0.8

1

1.8

19.5

24.5

0.0142

455

1

7×0.40

0.8

1

1.8

20

18.1

0.0135

480

1.5

7×0.50

0.8

1

1.8

21

12.1

0.0115

580

2.5

7×0.67

0.8

1

1.8

23.5

7.41

0.0093

780

4

7×0.85

1

1

1.8

28

4.61

0.0092

1125

6

7×1.04

1

1

1.8

30.5

3.08

0.0078

1450

12 Core CVV-S Control Cable


No.of core

Nominalcross- sectionalarea sq.mm²

No.&dia. Of wires No./mm

Thicknessof insulationmm

Thicknessof inner sheath mm

Thicknessof outer sheath mm

Overall diameter(Approx.)
mm

Maximumconductorresistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

12

0.5

7×0.30

0.8

1

1.8

18.5

36

0.0162

400

0.75

7×0.37

0.8

1

1.8

19.5

24.5

0.0142

460

1

7×0.40

0.8

1

1.8

20

18.1

0.0135

490

1.5

7×0.50

0.8

1

1.8

21

12.1

0.0115

595

2.5

7×0.67

0.8

1

1.8

23.5

7.41

0.0093

805

4

7×0.85

1

1

1.8

28

4.61

0.0092

1160

6

7×1.04

1

1

1.8

30.5

3.08

0.0078

1500



13 Core CVV-S Control Cable


No.of core

Nominalcross- sectionalarea sq.mm²

No.&dia. Of wires No./mm

Thicknessof insulationmm

Thicknessof inner sheath mm

Thicknessof outer sheath mm

Overall diameter(Approx.)
mm

Maximumconductorresistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

13

0.5

7×0.30

0.8

1

1.8

19

36

0.0162

435

0.75

7×0.37

0.8

1

1.8

20

24.5

0.0142

505

1

7×0.40

0.8

1

1.8

20.5

18.1

0.0135

530

1.5

7×0.50

0.8

1

1.8

22

12.1

0.0115

645

2.5

7×0.67

0.8

1

1.8

24.5

7.41

0.0093

875

4

7×0.85

1

1

1.8

29

4.61

0.0092

1275

6

7×1.04

1

1

1.9

32

3.08

0.0078

1665

14CoreCVV-SControlCable


No.of core

Nominalcross- sectionalarea sq.mm²

No.&dia.  of wires No./mm

Thicknessof insulationmm

Thicknessof inner sheath mm

Thicknessof outer sheath mm

Overall diameter(Approx.)
mm

Maximum conductorresistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

14

0.5

7×0.30

0.8

1

1.8

19

36

0.0162

435

0.75

7×0.37

0.8

1

1.8

20

24.5

0.0142

505

1

7×0.40

0.8

1

1.8

20.5

18.1

0.0135

540

1.5

7×0.50

0.8

1

1.8

22

12.1

0.0115

660

2.5

7×0.67

0.8

1

1.8

24.5

7.41

0.0093

900

4

7×0.85

1

1

1.8

29

4.61

0.0092

1305

6

7×1.04

1

1

1.9

32

3.08

0.0078

1715

15CoreCVV-SControlCable


No.of core

Nominalcross- sectionalarea sq.mm²

No.&dia. Of wires No./mm

Thicknessof insulationmm

Thicknessof inner sheath mm

Thicknessof outer sheath mm

Overall diameter(Approx.)
mm

Maximumconductorresistance(at20C)
Ohm/km

Minimum insulation resistance
(at70C)
Ohm/km

Cable weight
(Approx.)
kg/km

15

0.5

7×0.30

0.8

1

1.8

20

36

0.0162

475

0.75

7×0.37

0.8

1

1.8

21

24.5

0.0142

550

1

7×0.40

0.8

1

1.8

21.5

18.1

0.0135

585

1.5

7×0.50

0.8

1

1.8

23

12.1

0.0115

715

2.5

7×0.67

0.8

1

1.8

25.5

7.41

0.0093

980

4

7×0.85

1

1

1.8

30.5

4.61

0.0092

1425

6

7×1.04

1

1

1.9

34

3.08

0.0078

1875



The table of 0.6/1KV CVV-SWA shown concentric stranded conduct or only.If you want to have solid or flexible conduct or type, please contact with our Sales Department.