UL1015

UL1015

basic information
Detail
Application
The product is suitable for internal wiring of distribution cabinets, consoles, motors, transformers, etc.
 
Implementation of standards
UL 758


Technical parameters

Conductor Stranded or Solid Tinned Copper or Bare Copper .
Insulation PVC
Rated voltage 600V
Temperature range -30℃~+105℃
Test voltage AWG 24: 4kV
AWG 22,20: 5kV
AWG 18~10: 6kV
≥AWG 8: 7.5kV
Min bend radius One time:5×Cable diameter
Repeated:10×Cable diameter
Use in production of material does not contain cadmium and silicon resin, and free of paint moisture resistant properties of harmful substances, conforms to RoHS standard.
PVC self-extinguishing and flame retardant,  test method according to UL 1581,IEC 60332.


Specification range

AWG Conductor structure (number × diameter) Insulation Thickness (mm) Insulation diameter (mm) 20 ℃Max DC resistance of conductor (Ω×km) Package Length (m)
10 105×0.254 0.79 4.60 3.80 305
12 65×0.254 0.79 4.00 6.06
14 41×0.254 0.79 3.50 9.63
16 26×0.254 0.79 3.10 14.20
18 34×0.178 0.79 2.80 23.70
20 21×0.178 0.79 2.50 37.10
22 17×0.160 0.79 2.40 57.40
24 11×0.160 0.79 2.20 88.70
26 7×0.160 0.79 2.10 139.00
28 7×0.127 0.79 2.00 223.00