8.7/15Kv Single Core Cables according to IEC 60502

8.7/15Kv Single Core Cables according to IEC 60502

basic information
Detail
Application
The single core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 1,8/3KV to 26/35KV and frequency 50Hz, They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations,
 
Standards
IEC 60502 
 
Construction
Conductor: Plain annealed copper or aluminum complying with IEC 60228 class 1 or 2, 
Conductor Screen: The conductor screen consists of an extruded layer of non metallic, semi-conducting compound firmly bonded to the insulation to exclude all air voids, The conductor screen is not necessary for both PVC and EPR/HEPR insulated 1,8/3KV and 3,6/6KV cables,
Insulation: Insulation is of polyvinyl chloride (PVC) intended for 1,8/3KV and 3,6/6KV cables, cross-linked polyethylene compound (XLPE) or ethylene propylene rubber (EPR/HEPR),
 
Single core 8,7/15KV (Um=17,5KV)
Cable structure parameters

Unarmoured Cables

Nom. Cross-Section Area

Nom. Insulation Thickness

Copper Tape Thickness

Copper Wire Screen Area*

Nom. Sheath Thickness

Reference. Overall Diameter

Reference. Weight

CU

AL

mm²

mm

mm

mm²

mm

mm

kg/km

10

2.0

0.1

16

1.8

13

240

180

16

2.0

0.1

16

1.8

13

300

200

25

2.0

0.1

16

1.8

15

410

250

35

2.0

0.1

16

1.8

16

510

300

50

2.0

0.1

16

1.8

17

640

350

70

2.0

0.1

16

1.8

19

850

440

95

2.0

0.1

16

1.8

20

1130

540

120

2.0

0.1

16

1.8

22

1370

630

150

2.0

0.1

25

1.8

23

1650

730

185

2.0

0.1

25

1.8

25

2010

860

240

2.0

0.1

25

1.8

27

2570

1050

300

2.0

0.1

25

1.8

29

3160

1250

400

2.0

0.1

35

1.9

33

3980

1560

500

2.2

0.1

35

2.1

35.5

4910

1905

630

2.4

0.1

35

2.2

39.7

6340

2420